Development of Hybrid Fault Current Limiting Circuit Breaker with Environmentally Benign Gases

Research Project

Project/Area Number 13555080
Research Category

Grant-in-Aid for Scientific Research (B)

Allocation TypeSingle-year Grants
Section展開研究
Research Field 電力工学・電気機器工学
Research InstitutionNagoya University

Principal Investigator

MATSUMURA Toshiro  Nagoya University, Graduate School of Engineering, Professor, 工学研究科, 教授 (90126904)

Co-Investigator(Kenkyū-buntansha) SHIMIZU Hirotaka  Polytechnic University, Lecturer, 講師 (40314033)
YOKOMIZU Yasunobu  Nagoya University, Graduate School of Engineering, Associate Professor, 工学研究科, 助教授 (50230652)
Project Period (FY) 2001 – 2003
Project Status Completed (Fiscal Year 2003)
Budget Amount *help
¥3,800,000 (Direct Cost: ¥3,800,000)
Fiscal Year 2003: ¥1,900,000 (Direct Cost: ¥1,900,000)
Fiscal Year 2002: ¥1,900,000 (Direct Cost: ¥1,900,000)
KeywordsAlternative Gases of SF_6 / Global Warming / Circuit Breaker / Current Limiting / H_2 / Superconducting / Arc / 脱SF_6ガス / 環境低負荷 / 超電導 / CO_2ガス / 遮断機 / SF6ガス / 環境
Research Abstract

In the present study, a current-interruption experiment was performed to examine the interrupting capability for a hybrid circuit-breaker consisting of a load-break switch filled with H_2 and an air contactor connected in series. As far as the present experimental conditions are concerned, it is found that the hybrid model is capable of breaking a current with a peak value of 950 A. Compared with a double-switch model using Air in both quenching media which can interrupt a current with a peak value of 600 A, the current interrupting capability of the hybrid circuit-breaker was proved to be higher than that of the double-switch Air circuit-breaker due to the difference of the thermal and electrical conductivity between H_2 and Air. In other words, the hybrid model using Air and H_2 as arc-quenching media improves the interrupting performance. Furthermore, we have proposed a hybrid system in which a fault current limiter (FCL) and a circuit breaker (CB) are combined in' series. The present study describes the breaking ability of a small model of a hybrid fault current limiting circuit breaker (hybrid FCLCB), which consists of an air relay unit and a flux flow resistive type of a superconducting FCL unit with a high Tc B2223 bulk. We took two Bi2223 elements connected in series as the minimum configuration of the flux flow resistive type of the FCL and investigated the generation process of the flux flow resistance and the contact resistance. The current limiting breaking performance was investigated for the small model of the hybrid FCLCB that was constructed by connecting the minimum unit of the FCL to the relay contactor. The hybrid FCLCB for the 6.6 kV power distribution system was designed from the experimentally obtained results in the small model.

Report

(4 results)
  • 2003 Annual Research Report   Final Research Report Summary
  • 2002 Annual Research Report
  • 2001 Annual Research Report
  • Research Products

    (33 results)

All Other

All Publications (33 results)

  • [Publications] T.Matsumura: "Current interruption capability of H_2-air hybrid model circuit breaker"Vacuum. 73. 481-486 (2004)

    • Description
      「研究成果報告書概要(和文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] 平田 修一: "H_2-空気ハイブリッドアーク装置の電流遮断性能"電気学会放電・開閉保護・新エネルギー・環境合同研究会資料. SP-03-62. 17-21 (2003)

    • Description
      「研究成果報告書概要(和文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] 松村 年郎: "高温超伝導素子と継電器を用いた簡易限流遮断装置の遮断試験"平成16年電気学会全国大会論文集. 6. 171 (2004)

    • Description
      「研究成果報告書概要(和文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] 松村 年郎: "環境保全ガスの高温領域における放射係数"プラズマ応用科学. 10. 88-95 (2002)

    • Description
      「研究成果報告書概要(和文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] E.Calixte: "Assessment of Breaking performance of a Hybrid Fault Current-Limiting Circuit Breaker with Different Arc Parameters"Proc.of the 35^<th> Annual Conf., PES (IEEE'03). 545-551 (2003)

    • Description
      「研究成果報告書概要(和文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] T.Matsumura, et al.: "Current interruption capability of H2-air hybrid model circuit breaker"Vacuum. Vol.73. 481-486 (2004)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] S.Hirata, et al.: "Current Interruption Capability of H2-Air Hybrid Arc Quenching Device (in Japanese)"The Papers of Joint Technical Meeting, IEE Japan. ED-03-73/SP-03-62?FTE-03/17. 17-21 (2003)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] T.Matsumura, et al.: "Interruption Test of Small Hybrid Current Limiting Breaker Model Consisting of Relay and High Temperature Superconducting Element (in Japanese)"2004 National Convention Record IEE Japan. No.6-171. 301

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] T.Matsumura, et al.: "Emission Coefficients of Environmentally Benign Gases at High Temperature (in Japanese)"Applied Plasma Science. Vol.10. 88-95 (2002)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] E.Calixte et al.: "Assessment of Breaking Performance of a Hybrid Fault Current Limiting Circuit Breaker with Different Arc Parameters"Proc.of the 35th Annual Conf.PES (IEEE'03). 545-551 (2003)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] R.Hemmi, et al.: "Anode-Fall and Cathode-Fall Voltages of Air Arc in Atmosphere between Silver Electrodes"J.Phys.D : Appl.Phys.. Vol.36. 1097-1106 (2003)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] R.Hemmi, et al.: "Measurement of Dynamic Temperature on Anode Surface for Air Arc between Electrodes of Copper and Silver"Proc.of Institute of Applied Plasma Science (ISAPS'03), Kyoto Japan. 379-382 (2003)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] P.C.Aomiron, et al.: "Thermal-Breakdown Phenomennon in High Temperature CO2 and AIR under DC-Voltage Application"Proc.of the International Association of Science and Technology for Development (IASTED'03), New York USA. 76-80 (2003)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] E.Calixte, et al.: "Estimation of Interrupting Performance of Hybrid Fault Current-Limiting Circuit Breaker"Proc.of the International Association of Science and Technology for Development (IASTED'03), Marbella Spain. 273-278 (2003)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] R.Hemrni, et al.: "Electrode Fall Voltage of Air Arc in Atmosphere with Electrodes of Copper and Silver Containing Various Rates of Tin and Cadmium Oxides in Current Range from 10 to 100A"Proc.of 14th International Conference on Gas Discharges and Their Applications, Liverpool England. Vol.1. 23-26 (2002)

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      2003 Final Research Report Summary
  • [Publications] T.Matsumura: "Current interruption capability of H_2-air hybrid model circuit breaker"Vacuum. (to be printed). (2004)

    • Related Report
      2003 Annual Research Report
  • [Publications] E.Calixte: "Assessment of Breaking Performance of a Hybrid Fault Current-Limiting Circuit Breaker with Different Arc Paramenters"Proc.of the Thirty-Fifth Annual Conf, IEEE PES. 545-551 (2003)

    • Related Report
      2003 Annual Research Report
  • [Publications] E.Calixte: "Estimation of Interrupting Performance of Hybrid Fault Current-Limiting Circuit Breaker"Proc.of the International Association of Science and Technology for Development (IASTED'03). 273-278 (2003)

    • Related Report
      2003 Annual Research Report
  • [Publications] R.Hemmi: "Anode-Fall and Cathode-Fall Voltages of Air Arc in Atmosphere between Silver Electrodes"J.Phys.D : Appl.Phys. 36. 1097-1106 (2003)

    • Related Report
      2003 Annual Research Report
  • [Publications] 平田 修一: "H_2-空気ハイブリッドアーク装置の電流遮断性能"電気学会放電・開閉保護・新エネルギー・環境合同研究会資料. SP-03-62. 17-21 (2003)

    • Related Report
      2003 Annual Research Report
  • [Publications] 松村 年郎: "高温超伝導素子と継電器を用いた簡易限流遮断装置の遮断試験"平成16年電気学会全国大会論文集. 6. 171-171 (2004)

    • Related Report
      2003 Annual Research Report
  • [Publications] 逸見 礼: "Ag接点間大気中アークにおける陽極および陰極降下電圧の推定"電気学会 放電・開閉保護・新エネルギー・環境合同研究会資料. SP-02-03. 11-15 (2002)

    • Related Report
      2002 Annual Research Report
  • [Publications] R.Hemmi: "Anode-fall Voltages of Air Arcs between Electrodes of Cu, Ag and W at Currents uo to 1500A"Proc. of Int. Workshop on High Voltage Engineering (IWHV'03). SP-03-3. 13-18 (2003)

    • Related Report
      2002 Annual Research Report
  • [Publications] 平田 修一: "ハイブリッド構成によるアーク遮断能力の向上とその遮断過程"平成15年電気学会全国大会論文集. 6. 198 (2003)

    • Related Report
      2002 Annual Research Report
  • [Publications] 有竹 智宏: "磁束流抵抗型超伝導限流器の超伝導素子接続部分における損失評価"平成15年電気学会全国大会論文集. 5. 146 (2003)

    • Related Report
      2002 Annual Research Report
  • [Publications] 木村 彰宏: "小型空心2巻線超伝導限流起用コイルの試作"平成15年電気学会全国大会論文集. 5. 147 (2003)

    • Related Report
      2002 Annual Research Report
  • [Publications] Evenson calixte: "Breaking Duty Imposed on Circuit Breaker with Resistive Fault Current Limiter under Generator-Fed Fault Condition"平成15年電気学会全国大会論文集. 6. 253 (2003)

    • Related Report
      2002 Annual Research Report
  • [Publications] 松村 年郎: "環境調和型ガスを用いたハイブリッド電力用遮断器の提案"平成14年電気学会全国大会論文集. 6. 163 (2002)

    • Related Report
      2001 Annual Research Report
  • [Publications] 伊藤一将: "環境保全型ガス流安定化アークの残留電流"平成14年電気学会全国大会論文集. 6. 162 (2002)

    • Related Report
      2001 Annual Research Report
  • [Publications] Evenson Calixte: "Reduction Effect of Fault Current Limiter on Interrupting Condition of a Circuit breaker"平成14年電気学会全国大会論文集. 6. 164 (2002)

    • Related Report
      2001 Annual Research Report
  • [Publications] 木村 彰宏: "磁界印加機能付き空心2巻線型磁束拘束型限流器の限流動作特性に及ぼす故障発生位相角の影響"平成14年電気学会全国大会論文集. 5. 13 (2002)

    • Related Report
      2001 Annual Research Report
  • [Publications] 清水 洋隆: "磁束流抵抗型限流器における超伝導素子の必要体積に及ぼす素子特性の影響"平成14年電気学会全国大会論文集. 5. 12 (2002)

    • Related Report
      2001 Annual Research Report
  • [Publications] 野田 岳志: "交流縦磁界が印加されたBi2223高温超伝導バルクの交流臨界電流"平成14年電気学会全国大会論文集. 5. 25 (2002)

    • Related Report
      2001 Annual Research Report

URL: 

Published: 2002-04-01   Modified: 2016-04-21  