Simplified commissioning method of natural ventilation rate and systematic improvement method of the building operation using the method
Project/Area Number |
26249082
|
Research Category |
Grant-in-Aid for Scientific Research (A)
|
Allocation Type | Single-year Grants |
Section | 一般 |
Research Field |
Architectural environment/Equipment
|
Research Institution | Osaka University |
Principal Investigator |
|
Co-Investigator(Kenkyū-buntansha) |
山中 俊夫 大阪大学, 工学(系)研究科(研究院), 教授 (80182575)
桃井 良尚 大阪大学, 工学(系)研究科(研究院), 助教 (40506870)
小林 知広 大阪市立大学, 工学(系)研究科(研究院), 講師 (90580952)
Lim Eunsu 東洋大学, 理工学部, 准教授 (50614624)
|
Research Collaborator |
SAGARA Kazunobu 大阪大学, 大学院工学研究科, 教授
TANABE Shingo 大阪大学, 大学院生
|
Project Period (FY) |
2014-04-01 – 2017-03-31
|
Project Status |
Completed (Fiscal Year 2016)
|
Budget Amount *help |
¥40,040,000 (Direct Cost: ¥30,800,000、Indirect Cost: ¥9,240,000)
Fiscal Year 2016: ¥6,890,000 (Direct Cost: ¥5,300,000、Indirect Cost: ¥1,590,000)
Fiscal Year 2015: ¥19,240,000 (Direct Cost: ¥14,800,000、Indirect Cost: ¥4,440,000)
Fiscal Year 2014: ¥13,910,000 (Direct Cost: ¥10,700,000、Indirect Cost: ¥3,210,000)
|
Keywords | 自然換気 / 換気量 / コミッショニング / 実在建物 / 換気量測定 / 居住者評価 / 室内環境 / 換気口面積 / 現場測定 / 換気効率 |
Outline of Final Research Achievements |
Various measurement and estimation methods of natural ventilation rate were investigated in the real buildings. The method should be conducted for long period and is possible to validate the quantitative effect of the natural ventilation. The final goal of this study is to propose the simplified commissioning method of natural ventilation as the standard method. Measurement of the pressure differences at the wall was found to have enough accuracy for practical use. Compensation was possible of the measured pressure difference that is not go trough the outer wall. The estimation of the ventilation rate by the outer surface pressure and by the network calculation using the fixed indoor temperature obtained from BEMS were possible as well. Indoor air quality was verified to be increase during the natural ventilation usage from the long-term measurement of the indoor environment. Also a kind of the design charts of natural ventiation were proposed by network calculation.
|
Report
(4 results)
Research Products
(36 results)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
[Presentation] コーナーボイドを有する高層オフィスビルの自然換気性能に関する研究(その9)秋期における環境測定と居住者評価に基づく室内熱・空気環境の実態2014
Author(s)
環翼, 山中俊夫, 甲谷寿史, 桃井良尚, 相良和伸, 大森啓充, 田辺慎吾, 高山眞, 岡本尚, 田中規敏, 和田一樹
Organizer
空気調和・衛生工学会学術講演会
Place of Presentation
秋田大学(秋田市)
Year and Date
2014-09-03
Related Report
-