• Search Research Projects
  • Search Researchers
  • How to Use
  1. Back to previous page

DETERIORATION OF <Z_nO> TYPE DISTRIBUTION ARRESTER DUE TO THE CONTINUOUS HIGH FREQUENCY ABNORMAL VOLTAGE.

Research Project

Project/Area Number 60550205
Research Category

Grant-in-Aid for General Scientific Research (C)

Allocation TypeSingle-year Grants
Research Field 電力工学
Research InstitutionTOYOHASHI UNIVERSITY OF TECHNOLOGY

Principal Investigator

SAKAKIBARA TATEKI  TOYOHASHI UNI. OF TECH., PROFESSOR, 工学部, 助教授 (10023243)

Project Period (FY) 1985 – 1986
Project Status Completed (Fiscal Year 1986)
Budget Amount *help
¥2,100,000 (Direct Cost: ¥2,100,000)
Fiscal Year 1986: ¥400,000 (Direct Cost: ¥400,000)
Fiscal Year 1985: ¥1,700,000 (Direct Cost: ¥1,700,000)
KeywordsCV CABLE FAULT / INTERMITTENT ARC / TRANSIENT OVERVOLTAGE / CONTINUOUS OVERVOLTAGE / 定常異常電圧 / 中性点接地抵抗
Research Abstract

IN THIS RESEARCH, WE HAVE POINTED OUT THAT THE 6.6 kV CV CABLE SYSTEM BEHACES DIFFERENTLY FROM THE OVERHEAD SYSTEM UNDER THE ONE-LINE GROUND FAULT. THIS IS THE CASE BECAUSE THE 6.6 kV SYSTEM IS A CAPACITIVE CIRCUIT AND THERMAL DISINTEFRATION OF POLYETHYLENE AT THE FAULT POINT PRODUCES A VIGOROUSLY EJECTING ORGANIC GAS, WHICH HAS GREAT EFFECT ON THE ARC BEHAVIOR AT THE FAULT POINT. THUS THE FAULT ARC BECOMES AN INTERMITTENT ARC WHICH PRODUCES A COMPLICATED OVERVOLTAGE.
THIS RESEARCH HAS ANALYZED THE EFFECT OF INTERMITTENT ARC BY BOTH EXPERIMENTAL AND SIMULATION METHODS. THE TRANSIENT OVERVOLTAGE OF 6.6 kV NO-INSULATED NEUTRAL SYSTEM REACHES 3 pu. JUST AFTER THE FAULT OCCURRENCE AND THE STEADY-STATE OVERVOLTAGE REACHES 2.0 pu. TO SUPPRESS THEM BELOW 2 pu, IT IS NECESSARY TO GROUND THE NEUTRAL WITH A RESISTANCE OF LESS THAN 50 ohm.

Report

(1 results)
  • 1986 Final Research Report Summary
  • Research Products

    (2 results)

All Other

All Publications (2 results)

  • [Publications] SAKAKIBARA,TATEKI: PROC.INSTN ELECT.ENGRS.

    • Description
      「研究成果報告書概要(和文)」より
    • Related Report
      1986 Final Research Report Summary
  • [Publications] SAKAKIBARA, TATEKI: "OVERVOLTAGES DUE TO INTERMITTENT ARCING FAULTS IN 6.6 KV CV-CABLE SYSTEMS." PROC. INSTN ELECT. ENGRS.

    • Description
      「研究成果報告書概要(欧文)」より
    • Related Report
      1986 Final Research Report Summary

URL: 

Published: 1987-03-31   Modified: 2016-04-21  

Information User Guide FAQ News Terms of Use Attribution of KAKENHI

Powered by NII kakenhi