2014 Fiscal Year Final Research Report
Resistance, deformation behaviour and failure of high strength bolted connections in fire
Project/Area Number |
24560677
|
Research Category |
Grant-in-Aid for Scientific Research (C)
|
Allocation Type | Multi-year Fund |
Section | 一般 |
Research Field |
Building structures/materials
|
Research Institution | Chiba University |
Principal Investigator |
HIRASHIMA Takeo 千葉大学, 工学(系)研究科(研究院), 准教授 (20334170)
|
Project Period (FY) |
2012-04-01 – 2015-03-31
|
Keywords | 鋼構造 / 耐火設計 / 高力ボルト摩擦接合継手 / 最大引張耐力 / はしぬけ破断 / ボルトせん断破断 / 火災後冷却過程 / 構成要素モデル |
Outline of Final Research Achievements |
Resistance, deformation behaviour and failure of splice connections with high strength friction grip bolts exposed to fire were clarified by this experimental study. Maximum load from high temperature transient tests of the connection agreed with or slightly exceeded the calculated results based on the material test results under the strain rate of 7.5%/min. The ductility of the joints was larger for the thin-plate specimen (tear-out failure type) than for the thick-plate specimen (bolt in shear failure type) in case of not only the heating phase but also the cooling phase in fire. On the basis of these test results, the analytical model of the connection was proposed with the component-based method and the model was adopted in the program of structural fire behaviour for steel frames. This enables the analysis on the behaviour and robustness of steel frames on the connection behaviour in case of the fire.
|
Free Research Field |
建築耐火構造
|