Outline of Final Research Achievements |
A model low-voltage DC circuit breaker has been constructed to apply an insulated gate bipolar transistor to the direct-current interruption. The model circuit breaker functions limitation and interruption of the DC through a decrease in a gate-emitter voltage with an elapsed time at a certain time-constant. This research was performed to make the comprehensive elucidation on the current breaking properties. With regard to a current breaking property, the model circuit breaker designed with the time constant of 5 and 1 ms proved to accomplish the current interruption even for 300 A and even for the circuit inductance of 4.2 mH. Deriving an ohmic heat emerging during a current-limiting period allowed to find out the successful-interruption criterion that the ohmic heat energy is lower than 25 J or the current limiting time is longer than about 5 ms.
|
Free Research Field |
電気工学
|