2016 Fiscal Year Final Research Report
Evaluation of thermal environment improvement effect by desiccant air conditioning system
Project/Area Number |
15H06288
|
Research Category |
Grant-in-Aid for Research Activity Start-up
|
Allocation Type | Single-year Grants |
Research Field |
Architectural environment/Equipment
|
Research Institution | Toyohashi University of Technology |
Principal Investigator |
Nabeshima Yuki 豊橋技術科学大学, 工学(系)研究科(研究院), 助教 (10738800)
|
Project Period (FY) |
2015-08-28 – 2017-03-31
|
Keywords | 潜熱顕熱分離空調 / 稚内層珪質頁岩 / 浮遊真菌 / 無給水加湿 / 温熱環境計測 |
Outline of Final Research Achievements |
In order to evaluate thermal environment, power consumption evaluation and air quality evaluation of the desiccant system, a desiccant system was built in the laboratory. In summer season, the number of floating fungus during the operation of the desiccant system was investigated, and furthermore, changes in thermal environment due to humidification and power consumption were evaluated in winter. As a result of comparing the desiccant system and conventional air conditioning system, heating and humidification performance were confirmed. Indoor absolute humidity was larger than the outside air by about 2.0 g / kgDA.From this result, it was confirmed that no-feed water humidification was performed in winter. However, an effective reduction in power consumption was not seen. In addition, decreasing of the number of fungus was confirmed by dehumidifying ventilation system in the summer season.
|
Free Research Field |
建築設備
|