Energy Conservation Performance of CO2 Heat Pump in Cold Climate
Project/Area Number |
19560593
|
Research Category |
Grant-in-Aid for Scientific Research (C)
|
Allocation Type | Single-year Grants |
Section | 一般 |
Research Field |
Architectural environment/equipment
|
Research Institution | University of Toyama |
Principal Investigator |
HORI Yuji University of Toyama, 芸術文化学部, 准教授 (70432119)
|
Co-Investigator(Kenkyū-buntansha) |
桑澤 保夫 (独)建築研究所, 環境研究グループ, 上席研究員 (30251341)
|
Co-Investigator(Renkei-kenkyūsha) |
KUWASAWA Yasuo 独立行政法人建築研究所, 上席研究員 (30251341)
|
Project Period (FY) |
2007 – 2009
|
Project Status |
Completed (Fiscal Year 2009)
|
Budget Amount *help |
¥4,680,000 (Direct Cost: ¥3,600,000、Indirect Cost: ¥1,080,000)
Fiscal Year 2009: ¥390,000 (Direct Cost: ¥300,000、Indirect Cost: ¥90,000)
Fiscal Year 2008: ¥1,950,000 (Direct Cost: ¥1,500,000、Indirect Cost: ¥450,000)
Fiscal Year 2007: ¥2,340,000 (Direct Cost: ¥1,800,000、Indirect Cost: ¥540,000)
|
Keywords | 環境設計 / 省エネルギー / ヒートポンプ / 寒冷地 / 降雪地 / 除霜 / CO2ヒートポンプ給湯機 / エネルギー効率 / 北陸地域 / 給湯エネルギー / 実証実験 |
Research Abstract |
本研究課題では、寒冷地の気象条件が住宅用ヒートポンプ設備のエネルギー消費効率に与える影響について実証試験を行った。 実験の結果、低温多湿時の除霜によるエネルギー損失は5~10%程度生じており、特に外気温度-5℃~+5℃の範囲かつ高湿度状態で著しいことが明らかとなった。 この結果から、各地の気候における上記条件の出現頻度から、ヒートポンプ効率の低下を予測することを可能とした。
|
Report