• Search Research Projects
  • Search Researchers
  • How to Use
  1. Back to project page

1989 Fiscal Year Final Research Report Summary

Evaluation on the animal rooms with one way air-flow system.

Research Project

Project/Area Number 63480484
Research Category

Grant-in-Aid for General Scientific Research (B)

Allocation TypeSingle-year Grants
Research Field Laboratory animal science
Research InstitutionKagoshima University

Principal Investigator

YAMAUCHI Chuhei  Fac. of Med. Kagoshima UNIV., Asso. Prof., 医学部, 助教授 (00041377)

Co-Investigator(Kenkyū-buntansha) NOZOE Shinichi  Fac. of Med. Kagoshima UNIV., Asso. Prof., 医学部, 助教授 (10117533)
NOBORI Takuo  Fac. of Med. Kagoshima UNIV., Asso. Prof., 医学部, 助教授 (40094164)
AOYAMA Koji  Fac. of Med. Kagoshima UNIV., Assistant, 医学部, 助手 (70117472)
UEDA Tomoyuki  Fac. of Med. Kagoshima UNIV., Assistant, 医学部, 助手 (80160175)
Project Period (FY) 1988 – 1989
KeywordsLaboratory Animals / Animal Rooms / Air Current / Airborne Dust Particles / Ammonia / Airborne Bacteria / Allergy / Allergen
Research Abstract

We carried out a large survey on Laboratory Animal Allergy (LAA) in Japan 1987.1304 of the subjects, 23% had one or more allergic symptoms such as nasal, eyes, respiratory and skin symptoms.
As a example for the prevention of LAA, we developed an animal room with a one way air- flow system.
This study have practically evaluated the environmental conditions of various animal rooms which are reconstructed from conventional turbulent air flow system to one way air-flow system.
It was certified that the air in rooms flowed out directly from working area throughout the rack or cage to exhaust side. Static pressure in racks or cages are about 0.5 mmH_2O higher than exhaust side. Mean air velocity are 0.16m/sec at the holes of sliding door in front of the racks, 2.2m/sec at the holes of behind of the racks. Mean ventilation rate was 10.5 times/hr for the rooms, 92.7 times/hr for the cages. Temperature and humidity in the working area in rooms were the range of 20 -26゚C, 51- 69%, and they were slightly increased inside of the rack or cage. The number of airborne bacteria, airborne dust particle and ammonia in the working area in rooms decreased markedly than those before the reconstruction. Protein in the airborne dust in the working area was not detected. 83% of LAA subjects which developed LAA symptoms in animal rooms with turbulent air-flow systems became weak in the rooms with one way air-flow systems. Also, one way air-flow system created more comfortable environments for animals Serological monitoring for HVJ, MHV and M. plumonis in mice were negative for 12 months and these mice also showed no infectious finding their autopsy.
From the above results, we conclude that the animal room with one way air-flow systems serve to make comfortable environments for both the animals and the workers.

  • Research Products

    (6 results)

All Other

All Publications (6 results)

  • [Publications] Yamauchi C.,Obara T.,Fukuyama N.and Uede T.: "Evaluation of a one-way airflow system in an animal room based on counts of airborne dust particles and bacteria and measurements of ammonia levels." Laboratory Animals. 23. 7-15 (1989)

    • Description
      「研究成果報告書概要(和文)」より
  • [Publications] 花田武浩: "実験動物アレルギ-の臨床的、免疫的研究-とくにモルモット上気道アレルギ-を中心に-" 耳鼻臨床. 82. 1453-1464 (1989)

    • Description
      「研究成果報告書概要(和文)」より
  • [Publications] 山内忠平: "ビデオ実験動物アレルギ--現状と対策" 丸善(株), (1989)

    • Description
      「研究成果報告書概要(和文)」より
  • [Publications] Yamauchi C., Obara T., Fukuyama N. and Ueda T.: "Evaluation of a one-way air-flow system in an animal room based on counts of airborne dust particles and a measurements of ammonia levels." Laboratory Animals, 23, 7-15, 1989.

    • Description
      「研究成果報告書概要(欧文)」より
  • [Publications] Hnada takehiro: "Clinical and Immunologic Study of Patients Allergic to Laboratory Animals(LA A) - With Special Attention to Upper Airway Allergy to Guinea Pig -" Clinical Otorhinology, 82, 1453-1464, 1989.

    • Description
      「研究成果報告書概要(欧文)」より
  • [Publications] Yamauchi C.: "LAA:Laboratory Animal Allergy - The Current Status and Preventive Measures -" Telecast time (25 minutes) Medical School, Kagoshima University 1990.

    • Description
      「研究成果報告書概要(欧文)」より